DOI | https://doi.org/10.15407/pmach2025.01.019 |
Journal | Journal of Mechanical Engineering – Problemy Mashynobuduvannia |
Publisher | Anatolii Pidhornyi Institute of Power Machines and Systems of National Academy of Science of Ukraine |
ISSN | 2709-2984 (Print), 2709-2992 (Online) |
Issue | Vol. 28, no. 1, 2025 (March) |
Pages | 19-32 |
Cited by | J. of Mech. Eng., 2025, vol. 28, no. 1, pp. 19-32 |
Authors
Serhii M. Molskyi, Public Union “Refrigeration Association of Ukraine” (10, office 417, Druzhkivska str., Kyiv, 03113, Ukraine), e-mail: kriofor69@gmail.com, ORCID: 0009-0005-4363-8615
Oleksandr S. Molskyi, State Biotechnological University (44, Alchevskykh str., Kharkiv, 61000, Ukraine), e-mail: molskiyalex@gmail.com, ORCID: 0009-0001-1413-2931
Anna L. Vorontsova, Anatolii Pidhornyi Institute of Power Machines and Systems of NAS of Ukraine (2/10, Komunalnykiv str., Kharkiv, 61046, Ukraine), e-mail: vorontsova@ipmach.kharkov.ua, ORCID: 0000-0002-6521-3424
Abstract
Modern requirements for refrigeration equipment include the cessation of the use of systems with refrigerants that destroy the ozone layer, as well as a gradual reduction in the use of refrigerants with a high impact on global warming. The current task is to replace an environmentally unacceptable refrigerant with a neutral refrigerant for ozone and with a low global warming potential. The purpose of this paper is to develop and demonstrate a multivariate approach to the analysis of the specified problem – replacing HCFC and HFC refrigerants with refrigerants of the A2L group with a global warming potential below 500. Special attention is paid to the potential for increasing the productivity and energy efficiency of the refrigeration system. The following research tasks are solved in the paper: the impact of refrigerant replacement on the operation of the main elements of the system is determined; means and methods for increasing the cooling capacity of the refrigeration system when replacing the refrigerant are proposed; methods for increasing the energy efficiency of the refrigeration system are developed. The main changes in the operation of a refrigeration machine when replacing with a refrigerant of group A2L are identified in the paper. Namely, it is determined that the compressor performance changes, the lubricant needs to be replaced, it is necessary to take into account the influence of temperature glide, as well as changes in the operation of the condenser and evaporator. To increase the cooling capacity of a refrigeration machine, the following means and methods are proposed: selection of a refrigerant that can provide the required cooling capacity; increasing the compressor capacity either by frequency regulation or by installing an additional compressor; minimizing pressure losses in the hot steam and suction pipelines; reducing the temperature gradient on the condenser and evaporator; reducing the air temperature at the condenser inlet by adiabatic cooling; additional subcooling of the liquid refrigerant; optimizing the operating modes of the unit. The most effective method is determined – reducing the temperature difference between the condensation and boiling temperatures in the largest number of hours of the annual cycle.
Keywords: refrigerant, temperature glide, cooling capacity, global warming potential, adiabatic cooling.
Full text: Download in PDF
References
- Kharlampidi, D. Kh., Bratuta, E. G., & Sherstyuk, A. V. (2012). Raschet kharakteristik reversivnogo konditsionera-teplovogo nasosa pri perevode yego na alternativnyye khladagenty [Calculation of characteristics of a reversible air conditioner-heat pump when converting it to alternative refrigerants]. Integrirovannyye tekhnologii i energosberezheniye – Energy Technologies & Resource Saving, no. 3, pp. 78–83 (in Russian).
- Joashi, V., Prajapatir, S., & Bhatt, S. B. (2015). Experimental performance of air conditioner using refrigerant R410A as alternative for R22. International Journal of Advance Research in Engineering Science & Technology (IJAREST), vol. 2, iss. 4, pp. 304–308.
- Dang, Y., Kim, H.-S., Dang, C., & Hihara, E. (2015). Measurement of vapor viscosity of R1234yf and its binary mixture with R32, R125. International Journal of Refrigeration, vol. 58, pp. 131–136. https://doi.org/10.1016/j.ijrefrig.2015.06.010.
- Elgendy, E., Hassanain, M., & Fatouh, M. (2015). Assessment of R-438A as a retrofit refrigerant for R-22 indirect expansion water chiller. International Journal of Refrigeration, vol. 50, pp. 127–136. https://doi.org/10.1016/j.ijrefrig.2014.07.017.
- Hadya, B. (2016). Simulation of air conditioning system components and comparison of performance for three different refrigerants. International Journal of Research in Engineering and Applied Sciences (IJREAS), vol. 6, iss. 6, pp. 69–76.
- Ardita, I. N., Wirajati, I. G. A. B., Susila, I. D. M., & Sudirman, S. (2021). Performance analysis of retrofit R410A refrigerant with R32 refrigerant on a split air conditioner. Journal of Applied Mechanical Engineering and Green Technology, vol. 2, no. 1, pp. 1–4. https://doi.org/10.31940/jametech.v2i1.2459.
- Sutandi, T., Margana, A. S., Sumeru, K., & Sukri, M. F. (2020). Experimental study of R32 as a retrofit for R410A refrigerant in a residential air conditioner. Advances in Engineering Research, vol. 198, pp. 167–170. https://doi.org/10.2991/aer.k.201221.029.
- Nagaraju, P., Student, P. G., & Kumar, Ch. K. (2015). Experimental study on performance parameters for refrigerants R22, R410A, and R404A at various air outlet temperatures. International Journal of Engineering Research & Technology (IJERT), vol. 4, iss. 11, pp. 348–352. https://doi.org/10.17577/IJERTV4IS110372.
- Aziz, A., Thalal, A., & Mainil, A. K. (2018). Effect of cooling load on the performance of R22 residential split air conditioner when retrofitted with hydrocarbon refrigerant (HCR22). Journal of Advanced Research in Fluid Mechanics and Thermal Sciences, vol. 48, iss. 1, pp. 100–108.
- Makieieva, K. M. & Knysh, O. O. (2019). Obgruntuvannia zastosuvannia robochykh rechovyn «novoho pokolinnia» u vyparnykakh kholodylnykh i teplonasosnykh ustanovok [Justification of the use of “new generation” working substances in evaporators of refrigeration and heat pump units]. Kholodylna tekhnika ta tekhnolohiia – Refrigeration Engineering and Technology, vol. 55, iss. 4, pp. 211–216 (in Ukrainian). https://doi.org/10.15673/ret.v55i4.1633.
- (2014). New EU F-Gas Regulation (A-510-1). BITZER: official site. Germany: Kühlmaschinenbau GmbH, 12 p. https://www.bitzer.de/shared_media/documentation/a-510-1-2.pdf.
- (2022). ANSI ASHRAE Standard 34-2022 add a-2022. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE). https://www.ashrae.org/.
- (2023). BITZER Software v6.18.0 rev2811. BITZER: official site. https://www.bitzer.de/websoftware2.
- (2023). Refrigerant Report – Quick Guide (А-540-2). BITZER: official site. Germany: Kühlmaschinenbau GmbH. 12 p. https://www.bitzer.de/shared_media/images/topic-stories/2023_refrigerants/part2/Refrigerant-Report-Quick-Guide_2023-10-23.pdf.
- Kotzaoglanian, P. (2006). Manuel pratique de dépannage. Frigorifique, électrique et hydraulique. Manuel du dépanneur [Practical troubleshooting manual. Refrigeration, electrical and hydraulic. Troubleshooter’s manual]. Kotza International, 846 p. (in French).
- (2025). Coolselector®2. v.5.5.0: Danfoss Software: official site.
- Molskyi, S. M. (2022). Vyparnyi pereokholodzhuvach kholodylnoho ahentu [Evaporative subcooler of refrigerant]: patent for invention No. 126060; applied for on 03/25/2020, No. a201809347; published on 08/10/2022 (in Ukrainian).
- (2010). Influence of refrigerant subcooling on the refrigerating plant efficiency “Subcooling, but correctly!”: Gunter Technical Article. Germany: Gunter AG & Co.KG, 17 p.
- Reinders J. A. M. Heat exchange element WO-A1-2005/019739. 2003.
- Gogolin, A. A. (1966). Konditsionirovaniye vozdukha v myasnoy promyshlennosti [Air conditioning in the meat industry]. Moscow: Pishchevaya promyshlennost, 239 p. (in Russian).
- Kalyunov, V. S. & Tushev, K. A. (2007). Sistemy kholodosnabzheniya s ldoakkumultorami: realizatsiya trekh obyazatelnykh usloviy [Refrigeration supply systems with ice accumulators: implementation of three mandatory conditions]. Kholodilnaya tekhnika – Refrigeration Technology, vol. 96, no. 8, pp. 14–19 (in Russian).
- (2022). ECE /TRANS/WP.6/2022/6. Electric vehicle charging: CO2 emissions analysis. Note by the secretariat of the United Nations Economic Commission for Europe (UNECE). UN73 (Geneva, 15–17 June 2022).
- Reay, D. & Macmichael, D. (1978). Heat pumps: Design and applications. Oxford: Pergamon Press.
Received 04 February 2025
Accepted 28 February 2025
Published 30 March 2025